The subject of the entire investment is the housing of two electric power generators in a designed technological building. The building consists of the following rooms:

  • two independent engine halls, separated with a wall
  • pump station with exchange station
  • switchgear 0.4 kV
  • switchgear 15 kV
  • two rooms with unit transformers
  • auxiliary transformer rooms

Cogeneration generators will be located in soundproof rooms.
The engines will be powered by GZ-50 natural gas.
The generator unit will include:

  • heat recovery system from cooling water: engine housing, oil system and flue gas cooling
  • interstage cooling system of fuel mixture
  • emergency engine cooling system with the water/air cooler
  • fuel-air mixture cooling system after the 2nd stage (lost heat)
  • lubrication system
  • flue gas removal system
  • gas line
  • vantilation and combustion air system
  • gas detection system,
  • fire risk detection system


Charakterystyka agregatów prądotwórczych :

  • Manufacturer: GE Jenbacher
  • Type: JMS 616 GS-N.L
  • Electric power with 100% load: 2681 kV
  • Heat power to use together with heat reception from the combustion: 2615 kV
  • Gas usage with 100% load: 628 Nm3/h (with heat power provided in 1 Nm3 of fuel = 9.5 kWh/Nm3 )
  • Electrical efficiency: 44.9%


Engine’s specification:

  • working cycle: 4-stroke
  • number of cylinders: 16 V
  • engine speed: 1500 rpm
  • specific oil consumption: 0.55 kg/h
  • gas pressure in the inlet to the gas path: min. 1000 mbar (1 bar)
  • mass air demand for combustion: 11773 Nm3/h (15215kg/h)
  • dry flue gas flow: 14700 kg/h
  • wet flue gas flow: 15628 kg/h
  • flue gas temperature behind the exchanger: min. 1000 C
  • flue gas temperature in front of the exchanger: 3390 C


Power generator’s specification:

  • generator’s manufacturer: AVK
  • generator’s type: DIG 142e/4
  • generator’s voltage: 6300 V
  • nominal power with cos φ=1.0 : 2681 kW
  • frequency: 50 Hz
  • protection class: IP 23
  • efficiency coefficient with cos φ=1.0 : 97.7 %
  • generator cooling: air

Total weight during work: engine 31800 kg + generator 10250 kg